4-13

System Manual
C79000-G8576-C199-06

4.1.5

Technical Specifications

Important for the USA and Canada

The following approvals have been granted for the central controllers and
expansion units:

S

UL Listing Mark
Underwriters Laboratories (UL) to
Standard UL 508, Report E85972

S

CSA Certification Mark
Canadian Standards Association (CSA) to Standard
C 22.2 No. 142, Report LR 63533C

Unit safety

The unit complies with:

VDE 0160, IEC 1131-2

Protection against overvoltage
Overvoltage Class 2 (not with PS -3NA12)

VDE 0160 A1

Class of protection

I

Type of protection
(when empty slots are covered by dummy front plates)

IP 20 to IEC 529/DIN 40050

Climatic ambient conditions (tested to DIN IEC 68-2/-1/2/3)

Ambient temperature in operation
(supply air measured at lower air inlet of the unit)

0 to 55

°

C

Transportation and storage temperature

- 40 to 70

°

C

Temperature variation:

in operation
during transportation and storage
(when delivered at less than 0

o

C, at least 3 h

acclimatization because of possible

condensation)

10 K/h max.
20 K/h max.

Relative humidity:

in operation, during transportation and

storage

95% max. at 25

°

C, no condensation

Altitude:

in operation

during transportation and storage

- 1000 m to + 1500 m above sea level
(1080 hPa to 860 hPa)

- 1000 m bis + 3500 m above sea level
(1080 hPa to 660 hPa)

Pollutants:
SO

2

H

2

S

0,5 cm

3

/ m

3

, 4 days

0,1 cm

3

/ m

3

, 4 days

Mechanical ambient conditions (tested to DIN IEC 68-2-6)

Vibration during operation

10 to58 Hz (const. amplitude 0.075 mm)
58 to 500 HZ (const. acceleration 1g)

Central Controllers and Expansion Units Power Supply Units