In cases in which the higher-level power supply is not grounded, you must
connect the programmable controller to a separate protective
conductor/ground (e.g. foundation ground). Operation of the PLC with
non-floating power supplies is not allowed.

When connecting the power supplies, please note:
In 3 x 230 V systems, you may connect the power supply directly to two
phases.

Schrank

Control Power Supply

L+
L–

L1
L2

PE

L+/L1

L–/L2

PE

AC

DC

AC

AC

AC

DC

AC

DC

Non-Float-
ing Input

L1

L2

L3

PE

e.g. IT System (3 X 230V)

Programmable Controller

Protective Conductor Bar
in Cabinet

Low-Voltage Distribution,

24 to 230 V AC Load Supply
for AC Modules

5 to 60 V DC Load Supply
for Non-Floating DC Modules

Process I/Os

Protective
Conductor
Grounding

PS

CPU

U

0 V

int

А

Б

Б

Б

В

В

Г

Г

Д

Е

Non-Float-
ing Output

Floating
Input

Floating
Output

5 to 60 V DC Load Supply
for Floating DC Modules

Figure 3-10

Operating a Programmable Controller with Process I/Os from an Ungrounded Supply

In 3 x 400 V systems, a connection between phase and neutral conductor is
not allowed (excessively high voltage in the event of a ground fault).
Intermediate transformers should be used in these systems.