Part 2 Programs

2. Ladder

Statement

Field


[1] Extension

conditions

LD

LOAD

A

AND

O

OR

AB

AND

BLOCK

OB

OR

BLOCK

All of the above extension conditions can be used in non-ladder tasks.


[2] Ladder

commands

OUTR

Ladder output relay (Operand 1 = Output, flag number)

TIMR

Ladder timer relay (Operand 1 = Local flag number, Operand 2 =

Timer setting (sec))


3. Points

to

Note


 This system only processes software ladders using an interpreter. Therefore, the processing time is

much longer than that of a dedicated commercial sequencer.
(This system is not suitable for large-scale ladder processing.)

 If an extension condition is not specified for steps in which an input condition is specified, the steps will

be treated as LD (LOAD).

 Always specify a “normally ON” contact for those steps that must be processed without fail, such as

CHPR, TSLP and GOTO. (LD 7001)

Virtual input 7001: “Normally ON” contact



 The following circuit cannot be expressed. Create an equivalent circuit.






















Cannot be expressed.

1

2

3

OUTR301

OUTR302