Part 1 Installation

3.2 Starting via External Signal Selection





(1) Flow

chart



















































Select a desired program number externally and then input a start signal.

Controller

Power ON

READY signal

ON

Ready output

External device

Power ON

READY signal

confirmed?

Program number

confirmed?

Start signal
confirmed?

Program run

Emergency-stop

signal confirmed?

Controller

error?

Servo OFF

ALARM signal

ON

Alarm output

Emergency-stop

input

External start input

Program number

input

Various I/O

processing

Program number

specification

Start signal ON

Emergency-stop

switch ON?

Emergency-stop

signal ON

ALARM signal

confirmed?

ALARM

processing

Note) The assignments of dedicated

input/output port functions (such
as RDY output start signal) reflect
the factory settings.

When the READY signal (Output port No.
301) turns ON, the RDY lamp (green) on the
controller front panel will illuminate.

Input a desired program number as a BCD
code from the external device (Input port
Nos. 16 through 22).

Input a start signal (input port No. 0) from the
external device.

If the optional panel unit is connected, the
CODE display area indicates the program
number of each program that has been
started.

If an emergency-stop signal was input from
the external device or a controller error
occurred, the controller will turn off the servo
power. (The RDY lamp will turn off.)