Application Example 1

This application example demonstrates the temperature control for a system using two electric furnaces. The

set point (SP) of CH0 control is 200°C. The set point (SP) of CH1 control is 210°C.

• PID control is performed based on the temperature input to the PID module. The control output is turned on

or off in accordance with the output manipulated variable (MV).

• PID parameters (proportional band/proportional gain, integral time, derivative time, and ARW) are

automatically calculated using auto-tuning (AT).

• If the process variable (PV) of CH0 control becomes 205°C or higher, the upper limit alarm output (Q0) is

turned on and the control is disabled.

• If the process variable (PV) of CH1 control becomes 215°C or higher, the upper limit alarm output (Q1) is

turned on and the control is disabled.

System Configuration and Wiring

Wiring Example of the FC5A-F2M2 [Non-contact voltage output (for SSR drive)/current output type]





3-phase

Power Supply

CH0 Thermocouple

CH1 Thermocouple

+

-

+

-

SSR

SSR

+

-

+

-

Power
Supply

Electric

Furnace 2

Electric

Furnace 1

PID Module (FC5A-F2M2)

Channel

Terminal

No.

IN0

24V DC

OUT0

OUT1

IN1

Terminal

No.

Channel

Advertising