The pid module input does not operate normally, The pid module input does not operate normally -4 – IDEC MicroSmart Pentra User Manual

Page 145

Advertising
background image

T

ROUBLESHOOTING

8-4

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

The PID Module input does not operate normally.

Input does not operate normally.

Is the input wiring correct?

Correct the input wiring.

Does the sensor

malfunction?

Is the sensor or external

device connected to the PID

module securely?

Connect them securely.

Is the sensor burnt

out or the input signal source

abnormal?

Are sensor

specifications suitable with

the PID module?

Use a sensor with suitable
specifications.

Does AC leak into the

sensor circuit?

Call IDEC for assistance.

END

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

Replace the sensor.

Replace the sensor if it is burnt
out or disconnected.
(Make sure of input status.) *

Use an ungrounded type sensor.

Is there equipment that

interferes with or makes noise

near the PID module?

Take countermeasures against
inductive interference or noise.

Are the input type and

unit selected correctly?

Is the PV correction

value suitable?

Set it to a suitable value.

NO

NO

NO

YES

YES

Select them correctly.

YES

*1:

Refer to “Input Status Checking” on page 8-5.