Pid m – IDEC MicroSmart Pentra User Manual

Page 36

Advertising
background image

PID M

ODULE

M

AIN

F

UNCTIONS

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

4-13

Program Pattern

100

100

800

800

0

500

1000

60

60

300

30

10

0

10

0

0

1

2

3

10

10

10

10

200

200

200

200

50

50

50

50

50

50

50

50

0

0

0

0

0

10

0

10

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

100

100

100

100

0

0

0

0

1.0

1.0

1.0

1.0

0.0

0.0

0.0

0.0

Step No.

Set Point (SP)

Set Point

Wait Value
Proportional Term
Integral Time

ARW

Output MV Rate-of-Change

Alarm 1 Value

Output MV Upper Limit
Output MV Lower Limit

Cooling Proportional Band

Overlap/Dead Band

Time (Minutes)

C

Derivative Time

( )

Alarm 2 Value

Alarm 3 Value

Alarm 4 Value

Alarm 5 Value

Alarm 6 Value

Alarm 7 Value
Alarm 8 Value

(SP)

Program Pattern Example

The set point (SP) configured for each step is handled as the set point (SP) at the end of the step. The
time configured for each step is the process time of each step.
































When the program pattern is configured as shown in the above table, the following control is

performed at each step:

[Step 0]: The set point (SP) is gradually risen to 100

°C

in 60 minutes.

When the step 0 ends, the wait function works so that the program control does not

proceed to the step 1 until the process variable (PV) reaches 90

°C.

[Step 1]: The fixed value control is performed at 100

°C

of the set point (SP) for 60 minutes.

[Step 2]: The set point (SP) is gradually risen to 800

°C

in 5 hours.

When the step ends, the wait function works so that the program control does not proceed

to the step 3 until the process variable (PV) reaches 790°C.

[Step 3]: The fixed value control is performed at 800

°C

of the set point (SP) for 30 minutes.

Advertising