FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

5-19

Data Register Allocation - Blocks 4, 5 Initial Setting Parameters (SHOT Action)

Block 4 (CH0) and block 5(CH1) parameters are shown in the table below. Before changing the parameters of
block 4 or 5, it is recommended that the control of the PID module be disabled.

Offset from the

Control

Register

Parameter

Description

R/W

CH0

CH1

+53

+130 Control Action

0: Reverse control action (Heating)
1: Direct control action (Cooling)

R/W

+54

+131

Heating/Cooling Control
(CH0 only)

0: Disable
1: Enable

R/W

+55

+132

External SP Input
(CH0 only)

0: Disabled
1: External SP input (4 to 20mA DC)
2: External SP input (0 to 20mA DC)
3: External SP input (1 to 5V DC)
4: External SP input (0 to 1V DC)
5: Cascade control

R/W

+56

+133 Input Function

0: Input (CH0/CH1)
1: Difference input (CH0 - CH1)
2: Difference input (CH1 - CH0)
3: Addition input (CH0 + CH1)

R/W

+57

Output Function (CH0)

0: Output (CH0)
1: Output (CH1)
2: Both outputs (CH0, CH1)

R/W

+134 Output Function (CH1)

0: Output(CH1)
Output Function (CH0) has priority.

R/W

+58

+135 Input Type

See 5-21 for the input types and range

R/W

+59

+136

Set Point (SP) Upper Limit/
Linear Conversion Maximum
Value

When input is thermocouple or resistance thermometer:

Set point (SP) lower limit to input range upper limit

When input is voltage or current input:

Linear conversion minimum to input range upper limit

R/W

+60

+137

Set Point (SP) Lower Limit/
Linear Conversion Minimum
Value

When input is thermocouple or resistance thermometer:

Input range lower limit to set point (SP) upper limit

When input is voltage or current input:

Input range lower limit to linear conversion maximum

R/W

+61

+138 Output ON/OFF Hysteresis

When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current input:
1 to 1000

R/W

+62

+139

PV Correction

When input range unit is Celsius:
-100.0 to 100.0°C
When input range unit is Fahrenheit:
-100.0 to 100.0°F
When input is voltage or current input:
-1000 to 1000

R/W

+63

+140

PV Filter Time Constant

0.0 to 10.0 sec

R/W

+64

+141

Reserved

R/W

+65

+142

Alarm 1 Type

0: No alarm action
1: Upper limit alarm
2: Lower limit alarm
3: Upper/Lower limits alarm
4: Upper/Lower limit range alarm
5: Process high alarm
6: Process low alarm
7: Upper limit alarm with standby
8: Lower limit alarm with standby
9: Upper/Lower limits alarm with standby

R/W

+66

+143

Alarm 2 Type

R/W

+67

+144

Alarm 3 Type

R/W

+68

+145

Alarm 4 Type

R/W

+69

+146

Alarm 5 Type

R/W

+70

+147

Alarm 6 Type

R/W

+71

+148

Alarm 7 Type

R/W

+72

+149

Alarm 8 Type

R/W