A

PPENDIX

9-10

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

Blocks 4, 5 Initial Setting Parameters

Offset from

the Control

Register

Parameter

Default Value

CH0

CH1

+53

+130 Control Action

0: Reverse action (Heating)

+54

+131 Heating/Cooling Control (CH0 only)

[CH0] 0: Disable
[CH1] 0

+55

+132 External SP Input (CH0 only)

[CH0] 0: Disable
[CH1] 0

+56

+133 Input Function

[CH0/CH1] 0: Input (CH0/CH1)

+57

Output Function (CH0)

[CH0] 0: Output (CH0)

+134 Output Function (CH1)

[CH1] 0: Output (CH1)

+58

+135 Input Type

00h: Type K thermocouple -200 to 1370°C

+59

+136

Set Point (SP) Upper Limit/Linear Conversion
Maximum Value

1370°C (1370)

+60

+137

Set Point (SP) Lower Limit/Linear Conversion
Minimum Value

-200°C (-200)

+61

+138 Output ON/OFF Hysteresis

1.0°C (10)

+62

+139

PV Correction

0.0°C (0)

+63

+140

PV Filter Time Constant

0.0 seconds (0)

+64

+141

Reserved

0

+65

+142

Alarm 1 Type

0: No alarm action

+66

+143

Alarm 2 Type

+67

+144

Alarm 3 Type

+68

+145

Alarm 4 Type

+69

+146

Alarm 5 Type

+70

+147

Alarm 6 Type

+71

+148

Alarm 7 Type

+72

+149

Alarm 8 Type

+73

+150

Alarm 1 Hysteresis

1.0°C (10)

+74

+151

Alarm 2 Hysteresis

+75

+152

Alarm 3 Hysteresis

+76

+153

Alarm 4 Hysteresis

+77

+154

Alarm 5 Hysteresis

+78

+155

Alarm 6 Hysteresis

+79

+156

Alarm 7 Hysteresis

+80

+157

Alarm 8 Hysteresis

+81

+158

Alarm 1 Delay Time

0.0 seconds (0)

+82

+159

Alarm 2 Delay Time

+83

+160

Alarm 3 Delay Time

+84

+161

Alarm 4 Delay Time

+85

+162

Alarm 5 Delay Time

+86

+163

Alarm 6 Delay Time

+87

+164

Alarm 7 Delay Time

+88

+165

Alarm 8 Delay Time

+89

+166

AT Bias

20°C (20)

+90

+167

Control Mode

0: Fixed value control

+91

+168

Program Control Mode Start Type

0: PV start

+92

+169

Step Time Unit

0: Minute

+93

+170

Program End Action

0: Terminate program control

+94

+171

Proportional Term

0: Proportional band

+95

+172

Cooling Method (CH0 only)

[CH0] 0: Air cooling
[CH1] 0

+96

+173

Set Point (SP) when Program Control Starts 0.0°C (0)

+97

+174

Number of Repeats

0 times (0)

+98

+175

Cooling Output ON/OFF Hysteresis
(CH0 only)

[CH0] 1.0°C (10)
[CH1] 0

+99

+176

Output Specifications
(FC5A-F2M2 only)

0: Non-contact voltage output (for SSR

drive)

+100 +177

External SP Input Bias
(CH1 only)

[CH0] 0
[CH1] 0.0°C (0)

+101 +178

External SP Input Linear Conversion
Maximum Value (CH1 only)

[CH0] 0
[CH1] 1370°C (1370)

+102 +179

External SP Input Linear Conversion
Minimum Value (CH1 only)

[CH0] 0
[CH1] -200°C (-200)