Application example 3, Application example 3 -15, System configuration and wiring – IDEC MicroSmart Pentra User Manual

Page 136

Advertising
background image

A

PPLICATION

E

XAMPLES

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

7-15

Application Example 3

This application example demonstrates the heating/cooling control for a system using an electric furnace. The
set point (SP) of CH0 control is 200.0°C.

• PID control is performed based on the process variable (PV) of CH0 control. The heating output and cooling

output is turned on or off in accordance with heating output manipulated variable (MV) and cooling output
manipulated variable (MV).

• PID parameters (proportional band/proportional gain, integral time, derivative time, and ARW) are

automatically calculated using auto-tuning (AT).

• If the process variable (PV) of CH0 control becomes out of the range between 194.5°C and 205.5°C, the

upper/lower limits alarm output (Q0) is turned on and the control is disabled.


System Configuration and Wiring

Wiring Example of the FC5A-F2M2 [Non-contact voltage output (for SSR drive)/current output type]



3-phase

Power Supply

Cooling

Equipment

Electric

Furnace

Thermocouple

+

-

SSR

SSR

+

-

+

-

Power
Supply

PID Module (FC5A-F2M2)

IN1

OUT0

OUT1

IN0

Channel

Terminal

No.

24V DC

Terminal

No.

Channel