FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

7-11

3. Input CH0 Parameters

Configure the Input CH0 parameters in the PID Module Configuration dialog box. To open Input CH0

Parameters in the PID Module Configuration dialog box, click on Input Parameters (CH0) button or

Input (CH0) tab.

PID Module Configuration Dialog Box (Input CH0 Parameters)

Item

Setting

(1)

Input Range

Type K thermocouple, Celsius

(2)

Set Point (SP) Upper Limit

1370°C

(3)

Set Point (SP) Lower Limit

-200°C

(4)

Alarm 1 Type

Upper limit alarm

4. Control CH0 Parameters

Configure the Control CH0 parameters in the PID Module Configuration dialog box. To open Control
CH0 Parameters in the PID Module Configuration dialog box, click on Control Parameters (CH0)
button or Control (CH0) tab.


PID Module Configuration Dialog Box (Control CH0 Parameters)

Item

Setting

(1)

Control Mode

Program control mode

(1)

(1)

(2)

(3)

(4)