IDEC MicroSmart Pentra User Manual

Page 133

Advertising
background image

A

PPLICATION

E

XAMPLES

7-12

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

5. Program CH0 Parameters

Configure the Program CH0 parameters in the PID Module Configuration dialog box. To open Input
CH1 Parameters in the PID Module Configuration dialog box, click on Program (CH0) tab.

PID Module Configuration Dialog Box (Program CH0 Parameters)

Item

Setting

Step 0

Step 1

Step 2

Step 3

(1)

Set Point (SP)

100°C

100°C

800°C

800°C

(2)

Step Time

60 minutes

60 minutes

300 minutes

30 minutes

(3)

Wait Value

10°C

0°C

10°C

0°C

(4)

Alarm 1 Value

0°C

10°C

0°C

10°C

Notes:
• When the wait value is 0°C, the wait function is disabled.
• When the alarm value is 0°C, the alarm function is disabled.
• When a parameter for the program control except step time is changed in WindLDR, the parameter is

automatically copied to the following steps.


6. CH1 Parameters Setting

Configure CH1 Parameters in the same way as CH0.

7. Saving Parameters

Click OK button to save the configured parameters.

(1)
(2)
(3)

(4)

Advertising