IDEC MicroSmart Pentra User Manual

Page 51

Advertising
background image

D

EVICE

A

LLOCATION OF

PID

M

ODULE

5-10

FC5A MicroS

mart PID Module User’s Manual FC9Y-B1283

Data Register Allocation - Block 1 Write Only Parameters

The CPU module writes the following parameters stored in the data registers to the PID module every scan.

Offset from
the Control

Register

Parameter

Description

R/W

+20

CH0

Set Point (SP)

When the input is thermocouple or resistance thermometer:

Set point (SP) lower limit to set point (SP) upper limit

When the input is voltage or current input:

Linear conversion min. to linear conversion max.

W

+21

Manual Mode Output
Manipulated Variable

When heating/cooling control is disabled:

Output manipulated variable lower limit to output manipulated
variable upper limit

When heating/cooling control is enabled:

- Cooling output manipulated variable upper limit to heating
output manipulated variable upper limit

W

+22

Operation Parameter

Refer to the table below for the operation parameters

W

+23

CH1

Set Point (SP)

When the input is thermocouple or resistance thermometer:

Set point (SP) lower limit to set point (SP) upper limit

When the input is voltage or current input:

Linear conversion min. to linear conversion max.

W

+24

Manual Mode Output
Manipulated Variable

Output manipulated variable lower limit to output manipulated
variable upper limit

W

+25

Operation Parameter

Refer to the table below for the operation parameters

W

Note: When the power to the PID module is turned off, Block 1 parameters are cleared to zero.

Operation Parameters

Bit

Operation Parameters (1 word)

Item

Status

Description

Bit0

Control Enable Bit

0

Control disable

1

Control enable

Bit1

Auto-tuning (AT)/Auto-Reset Bit *1

0

Auto-tuning (AT)/Auto-reset cancel

1

Auto-tuning (AT)/Auto-reset perform

Bit2

Auto/Manual Mode Bit

0

Auto mode

1

Manual mode

Bit3

Program Control Bit

0

Program control stop

1

Program control run

Bit4

Program Hold Bit *2

0

Program control run

1

Program control hold

Bit5

External SP Input Enable Bit

0

External SP input disable

1

External SP input enable

Bit6

Advance Next Step Bit *3

0

No action

1

Program control advance next step

Bit7

Advance Previous Step Bit *4

0

No action

1

Program control advance previous step

Bit8 to
Bit15

Reserved

0

Fixed value 0

*1: Once auto-reset is performed, it cannot be cancelled during its performance.
*2: The program control is suspended while the program hold bit is on.
*3:
During the program control, the current step is terminated and the program control is proceeded to the start of the

next step when the advance next step bit is turned off to on.

*4: During the program control, the progression of the program control is moved back when the advance previous step

bit is turned off to on. If the elapsed time in the current step is less than 1 minute, the program control goes back to
the start of the previous step. If the elapsed time in the current step is more than or equal to 1 minute, the program
control goes back to the start of the current step. Even when the advance previous step is executed at Step 0, the
program control does not move back to Step 9 regardless of the program end action.