Pid m – IDEC MicroSmart Pentra User Manual

Page 35

Advertising
background image

PID M

ODULE

M

AIN

F

UNCTIONS

4-12

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

Action after Power Is Restored

When the power is restored, every bit of the operation parameter excluding the program hold bit stored in
the data register is maintained. If the power is failed and restored while the PID module performs the
program control, the PID module starts its operation in accordance with the original PID module status
before the power failure as shown in the table below.

Program End

Action

PID Module Status before the Power Failure

Standby

Status (*1)

Program

Control is

Performing.

Program Control is

suspended (Hold)

Program Control is

Terminated.

Terminate
Program Control

Standby
status is
maintained.

The program
control is
continued.
*2, *3

The program hold is
canceled, and the
program control is
continued. *2, *3

The program control is
started from the Step 0.

Continue
Program Control
(Repeat)

Hold Program
Control

The program hold is
maintained. Fixed value
control is performed with
the set point (SP) at the
time that the power is
turned off.


*1: The PID module is in standby status when the control enable bit is on but the program control bit is off. While in

standby status, the PID module performs no control.

*2: While the program control is running, the PID module saves the program control status every 6 minutes after the

program control is started (after the program control bit is turned on). The program control status is also saved at
the start of each step. If the power to the PID module is turned off while the program control is running, the PID
module resumes the program control from the latest saved point.



















For example, if the power to the PID module is turned off in 7 minutes after the program control is started at step
0, the PID module resumes the program control at the status (1) when the power is restored. If the power to the
PID module is turned off in 4 minutes after the program control enters step 1, the PID module resumes the
program control at the status (2) when the power is restored. If the power to the PID module is turned off in 2
minutes after the program control enters step 2, the PID module resumes the program control at the status (3),
which is the start of step 2, when the power is restored.


*3: To restart the program control from the start of step 0, turn off and on the program control bit (operation

parameter Bit3).

Step Number

Step Time

Program
Control Status
Saved Point

Elapsed Time
from Program
Control Start

0

1

2

3

10 min

3 min

(2)

(1)

(3)

4

15 min

6 min

10 min

24 min

28 min

6 min

12 min

25 min 30 min

34 min

18 min

0 min