Pid m – IDEC MicroSmart Pentra User Manual

Page 73

Advertising
background image

C

ONFIGURING

PID M

ODULE USING

W

IND

LDR

6-8

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

PID Module Configuration - Input Parameters List (CH0 and CH1)


The input parameters for CH0 and CH1 controls are described here.

Control Registers

Offset from

the control

register

Parameter

Description

R/W

CH0

CH1

(1)

+56

Input CH0 Function

0: Input CH0
1: Difference input (Input CH0 - Input CH1)
2: Difference input (Input CH1 - Input CH0)
3: Addition input (Input CH0 + Input CH1)

R/W

(2)

+133

Input CH1 Function

0: Input CH1
1: Difference input (Input CH0 - Input CH1)
2: Difference input (Input CH1 - Input CH0)
3: Addition input (Input CH0 + Input CH1)

R/W

+55

External SP Input

0: Disabled
1: External SP input (4 to 20mA DC) (Note)
2: External SP input (0 to 20mA DC)
3: External SP input (1 to 5V DC)
4: External SP input (0 to 1V DC)
5: Cascade control (Note)
Note: When External SP input is selected in Input CH1
Function,

“1: External SP input (4 to 20mA DC)” is

selected as the default. When Cascade Control is
selected in Input CH1 Function,

“5: Cascade control” is

selected.

R/W

(3)

+57

Output CH0 Function

0: Output CH0
1: Output CH1
2: Both outputs (Output CH0, Output CH1)

R/W

(4)

+134

Output CH1 Function

0: Output CH1
(The selection of Output CH0 Function has priority.)

R/W

(5)

+58

+135

Input Range

See page 6-10 for the detail about the input range.

R/W

(6)

+59

+136

Set Point (SP) Upper Limit/
Linear Conversion
Maximum Value

When input is thermocouple/resistance thermometer:

Set point (SP) lower limit to input range upper limit

When input is voltage/current:

Linear conversion minimum to input range upper limit

R/W


(1)

(2)

(3)

(4)

(5)

(6)

(7)

(8)

(9)

(10)

(11)

(12)

(13)