IDEC MicroSmart Pentra User Manual

Page 48

Advertising
background image

D

EVICE

A

LLOCATION OF

PID

M

ODULE

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

5-7

Data Register Allocation - Block 0 Read Only Parameters

The CPU module reads the following parameters from the PID module and store them in the data registers
every scan.

Offset from
the Control

Register

Parameter

Description

R/W

0

Common PID Module Operating Status

0000h: Initialization
0001h: Normal operation
0002h: External power supply error

R

+1

CH0

Current Process Variable (PV)

When input is normal:

Value within the control range (see 9-4)

When input is invalid: Unknown value

R

+2

Current Heating Output
Manipulated Variable (MV)

Output manipulated variable lower limit to upper
limit

R

+3

Current Cooling Output
Manipulated Variable (MV)

Cooling output manipulated variable lower limit
to upper limit

R

+4

Current Set Point (SP)

When input is thermocouple or resistance
thermometer:

Set point (SP) lower limit to set point (SP)
upper limit

When input is voltage or current input:

Linear conversion min. to linear conversion
max.

R

+5

Current Step Remaining Time

0 to 6000 minutes/seconds

R

+6

Current Step Number

0 to 9

R

+7

Remaining Repeat Number

0 to 10000

R

+8

Reserved

0 (Fixed value)

R

+9

Operation Parameter Monitor

See 5-8 for detail about the operation parameter
monitor.

R

+10

Operating Status

See 5-9 for detail about the operating status.

R

+11

CH1

Current Process Variable (PV)

When input is normal:

Value within the control range (see 9-4)

When input is invalid: Unknown value

R

+12

Current Output Manipulated
Variable (MV)

Output manipulated variable lower limit to
upper limit

R

+13

Current Set Point (SP)

When input is thermocouple or resistance ther-
mometer:

Set point (SP) lower limit to set point (SP)
upper limit

When input is voltage or current input:

Linear conversion min. to linear conversion
max.

R

+14

Current Step Remaining Time

0 to 6000 minutes/seconds

R

+15

Current Step Number

0 to 9

R

+16

Remaining Repeat Number

0 to 10000

R

+17

Reserved

0 (Fixed value)

R

+18

Operation Parameter Monitor

See 5-8 for detail about the operation
parameter monitor.

R

+19

Operating Status

See 5-9 for detail about the operating status.

R