6-17

PID Module Configuration - Output Parameters List (CH0 and CH1)


The output parameters for CH0 and CH1 are described here.

Output Parameters when Heating/Cooling Control is Enabled

Control Registers

Offset from

the control

register

Parameter

Description

R/W

CH0

CH1

(1)

+99

+176

Output Type

0: Non-contact voltage output (for SSR drive)
1: Current output

R/W

(2)

+30

+107

Control Period

1 to 120 sec

R/W

(3)

+46

+123

Output Manipulated
Variable Upper Limit

When output type is voltage:
Output manipulated variable lower limit to 100%
When output type is current:
Output manipulated variable lower limit to 105%

R/W

(4)

+47

+124

Output Manipulated
Variable Lower Limit

When output type is voltage:
0% to output manipulated variable upper limit
When output type is current:
-5% to output manipulated variable upper limit

R/W

(5)

+49

Cooling Control Period

1 to 120 sec

R/W