Pid m – IDEC MicroSmart Pentra User Manual

Page 93

Advertising
background image

C

ONFIGURING

PID M

ODULE USING

W

IND

LDR

6-28

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

SP

OFF

ON

OFF

ON

5

5

200

205

203

195

197

Alarm Hysteresis

Upper/Lower Limits Alarm with Standby

Alarm Value

Alarm Value

: Standby functions.

[Setting Example]

Set Point (SP)

: 2.0

Alarm 1 Value

: 200 C
: 5 C

Alarm 1 Hysteresis

C

Process Variable (PV) 203 : Alarm

Output OFF

C

197

C

Process Variable (PV) 195 : Alarm Output ON

C

C

205

Process Variable (PV) or

C

C

2.0

2.0

C

C

C

C

C

C

C

[Alarm Action]

Notes:
· When the set point (SP) is changed, the standby function is enabled. Once the process variable (PV)

enters the alarm output off range, the standby function is canceled.

· Even when an alarm output is triggered, the PID module continues its control. To stop the control when an

alarm is triggered, ladder programming is needed. For a ladder program example, see 7-6.

(7) Control Register+37: Alarm 1 Value

Control Register+38: Alarm 2 Value
Control Register+39: Alarm 3 Value
Control Register+40: Alarm 4 Value
Control Register+41: Alarm 5 Value
Control Register+42: Alarm 6 Value
Control Register+43: Alarm 7 Value
Control Register+44: Alarm 8 Value

There are two types of alarms: Deviation alarm and process alarm.

Alarm Type

Alarm Value

Alarm Action

Deviation
Alarm

Upper/Lower limit range alarm

Deviation from the set
point (SP) is the alarm
value.

The alarm output turns off if the
process variable (PV) exceeds
the range.

Upper limit alarm,
Lower limit alarm,
Upper/Lower limits alarm,
Upper limit alarm with standby,
Lower limit alarm with standby,
Upper/Lower limits alarm with
standby

The alarm output turns on if the
process variable (PV) exceeds
the range.

Process
Alarm

Process high alarm
Process low alarm

The alarm action point is
the alarm value.

The alarm output turns on if the
process variable (PV) exceeds
the alarm value.


When the alarm value is 0, the alarm action is disabled except process high alarm and process low alarm.
If the input type or input unit type is changed, confirm the valid range of the alarm value and configure
appropriate values.