C5A MicroSmart PID Module User’s Manual FC9Y-B1283

6-5

User Program Upload

When the user program containing the initial parameters of the PID modules is uploaded from the CPU

module, the initial values will be restored. The parameters saved in the PID module will not be read.

How to restore data register values when a keep data error has occurred

If more than 30 days pass since the power to the CPU module is turned off, values stored in the data

registers will be lost. When the data register values are lost, after the power is turned on, restore the PID

module parameters in the data registers of the CPU module using either of the following methods, and

then enable the control of the PID module.

Method 1: Use the parameters stored in the PID module

The parameters stored in the PID module can be read out and stored in the data registers of the CPU

module with one of the following procedures:

Procedure 1: Using WindLDR

1. Open Expansion Modules Configuration dialog box in WindLDR.

2. Select the slot number of the connected PID module and open the PID Module Configuration dialog

box.

3. Click on Read All Parameters button to read all parameters from the PID module.

4. Configure the set point (SP) and the manual mode output manipulated variable in the PID Module

Configuration dialog box. *1

5. Click on Write All Parameters button.

When the control of the PID module is enabled, the PID module will start operating with the

downloaded parameters.

Procedure 2: Using the user program

1. Turn off to on the reading all parameters relay (control relay + 0).

2. Configure the set point (SP) and the manual mode output manipulated variable if necessary. *1

When the control of the PID module is enabled, the PID module will start operating with the

configured parameters.

*1: Because the block 1 parameters are not saved in the PID module, it is required to configure those parameters.

Method 2: Use the default parameters stored in the ROM of the CPU module

When the PID module parameters are configured in the PID Module Configuration dialog box and the

user program is downloaded to the CPU module, the PID module parameters (initial values) will be

saved in ROM of the CPU module. Those initial values can be loaded to the data registers in the CPU

module, and the PID module can be operated with those initial values with the following procedure:

1. Turn off to on the loading initial values relay (control relay + 1).

2. Turn off to on the writing all parameters relay (control relay + 2).

When the control of the PID module is enabled, the PID module will start operating with the default

values.