FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

7-9

PID Module Parameter Configuration

The parameters of the PID module can be configured in the Expansion Modules Configuration and PID

Module Configuration dialog boxes. The procedure to configure the PID module is described below.

Parameter Configuration Example

Quantity of Modules: 1 unit

Slot No.:

Slot 1

Module Type No.:

FC5A-F2MR2

Data Register:

D1000

Internal Relay:

M1000

I/O Function:

Used as a 2-channel PID module

CH0

CH1

Input

Type K thermocouple (-200 to 1370)°C

Type K thermocouple (-200 to 1370)°C

Output

Relay output

Relay output

Alarm 1 Type

Upper limit alarm

Upper limit alarm

Program Pattern: Settings are common between CH0 and CH1.

Step 0

Step 1

Step 2

Step 3

Set Point (SP)

100°C

100°C

800°C

800°C

Step Time

60 minutes

60 minutes

300 minutes

30 minutes

Wait Value

10°C

0°C

10°C

0°C

Alarm 1 Value

0°C

10°C

0°C

10°C