FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

5-17

Data Register Allocation - Blocks 2, 3 Basic Parameters (SHOT Action)

Block 2 (CH0) and block 3 (CH1) parameters are shown in the table below. The parameters of block 2 and 3
can be changed while the control of the PID module is enabled.

Offset from the

Control

Register

Parameter

Description

R/W

CH0

CH1

+26

+103 Proportional Term

Proportional band:
When input range unit is Celsius:
0 to 10000°C
(Range with a decimal point: 0.0 to 1000.0°C)
When input range unit is Fahrenheit:
0 to 10000°F
(Range with a decimal point: 0.0 to 1000.0°F)
When input is voltage or current input:
0.0 to 1000.0%
Proportional gain:
0.00 to 100.00%

R/W

+27

+104 Integral Time

0 to 10000 sec

R/W

+28

+105 Derivative Time

0 to 10000 sec

R/W

+29

+106 ARW (Anti-Reset Windup)

0 to 100%

R/W

+30

+107 Control Period

1 to 120 sec

R/W

+31

+108 Reset

When input range unit is Celsius:
-100.0 to 100.0 °C
When input range unit is Fahrenheit:
-100.0 to 100.0 °F

When input is voltage or current input:
-1000 to 1000

R/W

+32

+109

Output Manipulated Variable
Rate-of-Change

0 to 100%/sec

R/W

+33

+110

Set Point (SP) Rise Rate

When input range unit is Celsius:
0 to 10000°C/min
(Range with a decimal point: 0.0 to 1000.0°C/min)
When input range unit is Fahrenheit:
0 to 10000°F/min
(Range with a decimal point: 0.0 to 1000.0°F/min)
When input is voltage or current input:
0 to 10000/min

R/W

+34

+111

Set Point (SP) Fall Rate

When input range unit is Celsius:
0 to 10000°C/min
(Range with a decimal point: 0.0 to 1000.0°C/min)
When input range unit is Fahrenheit:
0 to 10000°F/min
(Range with a decimal point: 0.0 to 1000.0°F/min)
When input is voltage or current input:
0 to 10000/min

R/W

+35

+112

Loop Break Alarm (LA) Time 0 to 200 minutes

R/W

+36

+113

Loop Break Alarm (LA) Span

When input range unit is Celsius:
0 to 150 °C
(Range with a decimal point: 0.0 to 150.0°C)
When input range unit is Fahrenheit:
0 to 150 °F
(Range with a decimal point: 0.0 to 150.0°F)
When input is voltage or current input:
0 to 1500

R/W

+37

+114

Alarm 1 Value

See 5-18 for the valid range of alarm 1 to alarm 8 values.

R/W

+38

+115

Alarm 2 Value

R/W

+39

+116

Alarm 3 Value

R/W

+40

+117

Alarm 4 Value

R/W

+41

+118

Alarm 5 Value

R/W

+42

+119

Alarm 6 Value

R/W

+43

+120 Alarm 7 Value

R/W

+44

+121 Alarm 8 Value

R/W

+45

+122 Reserved

R/W