Pid m – IDEC MicroSmart Pentra User Manual

Page 84

Advertising
background image

C

ONFIGURING

PID M

ODULE USING

W

IND

LDR

F

C5A MicroSmart PID Module User’s Manual FC9Y-B1283

6-19

PID Module Configuration - Program Parameters List (CH0 and CH1)


Program parameters for CH0 and CH1 are described here.

Control Registers

Offset from

the control

register

Parameter

Description

R/W

CH0

CH1

(1)

+180

+390

Set Point (SP)

When input is thermocouple/resistance thermometer:

Set point (SP) lower limit to set point (SP) upper limit

When input is voltage or current:

Linear conversion min. to linear con- version max.

R/W

(2)

+181

+391

Step Time

When step time unit is Minute:

0 to 6000 minutes

When step time unit is Second:

0 to 6000 seconds

R/W

(3)

+182

+392

Wait Value

When input range unit is Celsius:
0 to 100°C
(Range with a decimal point: 0.0 to 100.0°C)
When input range unit is Fahrenheit:
0 to 100°F
(Range with a decimal point: 0.0 to 100.0°F)
When input is voltage or current:
0 to 1000

R/W

(4)

+183

+393

Proportional Band/
Proportional Gain

Proportional band:
When input range unit is Celsius:
0 to 10000°C
(Range with a decimal point: 0.0 to 1000.0°C )
When input range unit is Fahrenheit:

0 to 10000°F

(Range with a decimal point: 0.0 to 1000.0°F)
When input is voltage or current:
0.0 to 1000.0%
Proportional gain:
0.00 to 100.00%

R/W

(5)

+184

+394

Integral Time

0 to 10000 sec

R/W

(6)

+185

+395

Derivative Time

0 to 10000 sec

R/W

(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
(19)
(20)