D

EVICE

A

LLOCATION OF

PID

M

ODULE

5-18

FC5A MicroS

mart PID Module User’s Manual FC9Y-B1283

+46

+123

Output Manipulated Variable
Upper Limit

When output type is relay or voltage:
Output manipulated variable lower limit to 100%
When output type is current:
Output manipulated variable lower limit to 105%

R/W

+47

+124

Output Manipulated Variable
Lower Limit

When output type is relay or voltage:
0% to output manipulated variable upper limit
When output type is current:
-5% to output manipulated variable upper limit

R/W

+48

+125

Cooling Proportional Band
(CH0 only)

0.0 to 10.0 times
(Cooling proportional band is the multiplication of heating
proportional band)

R/W

+49

+126

Cooling Control Period
(CH0 only)

1 to 120 sec

R/W

+50

+127

Overlap/Dead Band
(CH0 only)

When input range unit is Celsius:
-200.0 to 200.0°C
When input range unit is Fahrenheit:
-200.0 to 200.0°F
When input is voltage or current input:
-2000 to 2000

R/W

+51

+128

Cooling Output Manipulated
Variable Upper Limit
(CH0 only)

When output type is relay or voltage:
Cooling output manipulated variable lower limit to 100%
When output type is current:
Cooling output manipulated variable lower limit to 105%

R/W

+52

+129

Cooling Output Manipulated
Variable Lower Limit
(CH0 only)

When output type is relay or voltage:
0% to cooling output manipulated variable upper limit
When output type is current:
-5% to cooling output manipulated variable upper limit

R/W


Valid Range for Alarm 1 to Alarm 8 Settings












*1: When input is voltage/current, full scale is the linear conversion span.
*2: When input is voltage/current, the valid range is the linear conversion minimum value to linear conversion

maximum value.


Alarm Type

Valid Range

Upper Limit Alarm

–(Full scale) to full scale *1

Lower Limit Alarm

–(Full scale) to full scale *1

Upper/Lower Limits Alarm

0 to full scale *1

Upper/Lower Limit Range Alarm

0 to full scale *1

Process High Alarm

Input range lower limit to input range upper limit *2

Process Low Alarm

Input range lower limit to input range upper limit *2

Upper Limit Alarm with Standby

–(Full scale) to full scale *1

Lower Limit Alarm with Standby

–(Full scale) to full scale *1

Upper/Lower Limits Alarm with Standby

0 to full scale *1