IDEC MicroSmart Pentra User Manual

Page 123

Advertising
background image

A

PPLICATION

E

XAMPLES

7-2

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

PID Module Parameter Configuration

The parameters of the PID module can be configured in the Expansion Modules Configuration and PID

Module Configuration dialog boxes. The procedure to configure the PID module is described below.

Parameter Configuration Example

Quantity of Modules: 1 unit

Slot Number:

Slot 1

Module Type No.:

FC5A-F2M2

Data Register:

D1000

Internal Relay:

M1000

I/O Function:

Used as a 2-channel PID module

CH0

CH1

Input

Type K thermocouple (-200 to 1370)°C

Type K thermocouple (-200 to 1370)°C

Output

Non-contact voltage output (for SSR drive)

Non-contact voltage output (for SSR drive)

Alarm 1 Type

Upper limit alarm

Upper limit alarm

Alarm 1 Value

5°C

5°C

Set Point (SP)

200°C

210°C

Control Action

PID control action [P, I, D and ARW are
automatically calculated using auto-tuning
(AT)]

PID control action [P, I, D and ARW are
automatically calculated using auto-tuning
(AT)]

AT Bias

20°C

20°C


Parameter Configuration Procedure

1. Expansion Modules Configuration

Select Configuration > Expansion Modules from the WindLDR menu bar to open the Expansion

Modules Configuration dialog box.

In the Expansion Modules Configuration dialog, configure the quantity of modules, slot number, module

type number, control register (data register) and control relay (internal relay). Click on Configure

Parameters button to open the PID Module Configuration dialog box.

Expansion Modules Configuration Dialog Box

Item

Setting

(1)

Quantity of Modules

1

(2)

Slot No.

Slot 1

(3)

Module Type No.

FC5A-F2M2

(4)

Data Register

D1000

(5)

Internal Relay

M1000

(1)

(2)

(3)

(4)

(5)

Advertising