IDEC MicroSmart Pentra User Manual

Page 50

Advertising
background image

D

EVICE

A

LLOCATION OF

PID

M

ODULE

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

5-9

Operating Status

Bit

Operating Status (1 word)

Parameter

Status

Description

Bit0

(Heating) Control Output

0

OFF

1

ON (Unknown for current output)

Bit1

Cooling Control Output
(CH0 only)

0

OFF

1

ON (Unknown for current output)

Bit2

Loop Break Alarm

0

Normal operation

1

Loop break alarm is occurring

Bit3

Over Range

0

Normal operation

1

Input value is exceeding the upper limit of the
control range (See page 9-4).
Thermocouple or resistance thermometer may be
burnt out. Voltage input (0 to 1V DC) may be
disconnected.

Bit4

Under Range

0

Normal operation

1

Input value is below the lower limit of the control
range (See page 9-4).
Voltage input (0 to 5V DC) may be disconnected.
Current input (4 to 20mA DC) may be discon-
nected.

Bit5

Program Wait

0

Normal operation

1

Program wait is functioning

Bit6

Program End Output

0

OFF

1

ON

Bit7

Alarm 1 Output

0

OFF

1

ON

Bit8

Alarm 2 Output

0

OFF

1

ON

Bit9

Alarm 3 Output

0

OFF

1

ON

Bit10

Alarm 4 Output

0

OFF

1

ON

Bit11

Alarm 5 Output

0

OFF

1

ON

Bit12

Alarm 6 Output

0

OFF

1

ON

Bit13

Alarm 7 Output

0

OFF

1

ON

Bit14

Alarm 8 Output

0

OFF

1

ON

Bit15

Reserved

0

0 (Fixed value)