IDEC MicroSmart Pentra User Manual

Page 61

Advertising
background image

D

EVICE

A

LLOCATION OF

PID

M

ODULE

5-20

FC5A MicroS

mart PID Module User’s Manual FC9Y-B1283

+73

+150

Alarm 1 Hysteresis

When input range unit is Celsius:

0.1 to 100.0°C

When input range unit is Fahrenheit:

0.1 to 100.0°F

When input is voltage or current input:
1 to 1000

R/W

+74

+151

Alarm 2 Hysteresis

R/W

+75

+152

Alarm 3 Hysteresis

R/W

+76

+153

Alarm 4 Hysteresis

R/W

+77

+154

Alarm 5 Hysteresis

R/W

+78

+155

Alarm 6 Hysteresis

R/W

+79

+156

Alarm 7 Hysteresis

R/W

+80

+157

Alarm 8 Hysteresis

R/W

+81

+158

Alarm 1 Delay Time

0 to 10000 sec

R/W

+82

+159

Alarm 2 Delay Time

R/W

+83

+160

Alarm 3 Delay Time

R/W

+84

+161

Alarm 4 Delay Time

R/W

+85

+162

Alarm 5 Delay Time

R/W

+86

+163

Alarm 6 Delay Time

R/W

+87

+164

Alarm 7 Delay Time

R/W

+88

+165

Alarm 8 Delay Time

R/W

+89

+166

AT Bias

When input range unit is Celsius:
0 to 50 °C (0.0 to 50.0°C for input with decimal point)
When input range unit is Fahrenheit:
0 to 100 °F (0.0 to 100.0°F for input with decimal point)

R/W

+90

+167

Control Mode

0: Fixed value control mode
1: Program control mode

R/W

+91

+168

Program Control Mode Start
Type

0: PV start
1: PVR start
2: SP start

R/W

+92

+169

Step Time Unit

0: Minute
1: Second

R/W

+93

+170

Program End Action

0: Terminate program control
1: Continue program control (Repeat)
2: Hold program control

R/W

+94

+171

Proportional Term

0: Proportional band
1: Proportional gain

R/W

+95

+172

Cooling Method
(CH0 only)

0: Air cooling
1: Oil cooling
2: Water cooling

R/W

+96

+173

Set Point (SP) when Program
Control Starts

When input is thermocouple or resistance thermometer:

Set point (SP) lower limit to set point (SP) upper limit

When input is voltage or current input:

Linear conversion min. to linear conversion max.

R/W

+97

+174

Number of Repeats

0 to 10000 times

R/W

+98

+175

Cooling Output ON/OFF
Hysteresis
(CH0 only)

When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current input:

1 to 1000

R/W

+99

+176

Output Type
(FC5A-F2M2 only)

0: Non-contact voltage output (for SSR drive)
1: Current output

R/W

+100

+177

External SP Input Bias
(CH1 only)

±20% of the external SP input linear conversion span

R/W

+101

+178

External SP Input Linear
Conversion Maximum Value
(CH1 only)

External SP input Linear conversion min. to input range
upper limit

R/W

+102

+179

External SP Input Linear
Conversion Minimum Value
(CH1 only)

Input range lower limit to external SP input linear conversion
max.

R/W