IDEC MicroSmart Pentra User Manual

Page 147

Advertising
background image

T

ROUBLESHOOTING

9-6

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

Loop break alarm turns on even though the actuator operates normally.

Loop break alarm turns on

even though the actuator is

operating normally.

Is the loop break

alarm time too short? (*1)

Set the loop break alarm time to a
suitable value.

Is the loop break

alarm span too great? (*2)

Call IDEC for assistance.

END

YES

NO

Set the loop break alarm span to a
suitable value.

NO

YES

*1: Loop break alarm time may be too short compared to the loop break alarm span.
*2: Loop break alarm span may be too great compared to the loop break alarm time.


Note: Loop break alarm time and loop break alarm span

Set the loop break alarm span to a value around 1.25 times bigger than the operation span in normal
operation.


Example: Heater in which temperature rises 150°C in 30 minutes

When the loop break alarm time is 10 minutes, the operation span in normal operation is 50°C
(150°C/30 minutes × 10 minutes). Set the loop break alarm span to 65°C which is about 1.25
times bigger than 50°C.


Program control is terminated earlier than the configured time.

Program control is terminated
earlier than the configured time.

Is PV start (*1) or

PVR start (*1) selected as “program

control mode start type“?

Select SP start (*1) as “program
control mode start type“.

Is each step time suitable?

Call IDEC for assistance.

END

YES

NO

Set each step time to a suitable
value.

YES

NO

*1: For program control mode start type, see page 6-41.