Pid m – IDEC MicroSmart Pentra User Manual

Page 80

Advertising
background image

C

ONFIGURING

PID M

ODULE USING

W

IND

LDR

F

C5A MicroSmart PID Module User’s Manual FC9Y-B1283

6-15

Offset from

the control

register

Parameter

Setting Range

R/W

CH0

CH1

(14)

+32

+109

Output Manipulated
Variable Rate-of-Change

0 to 100%/sec

R/W

(15)

+61

+138

Output ON/OFF
Hysteresis

When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current:
1 to 1000

R/W

(16)

+21

+24

Manual Mode Output
Manipulated Variable

When heating/cooling control is disabled:
Output manipulated variable lower limit to output

manipulated variable upper limit

When heating/cooling control is enabled:

- Cooling output manipulated variable upper limit to
heating output manipulated variable upper limit

R/W

(17)

+35

+112

Loop Break Alarm (LA)
Time

0 to 200 minutes

R/W

(18)

+36

+113

Loop Break Alarm (LA)
Span

When input range unit is Celsius:
0 to 150 °C
(Range with a decimal point: 0.0 to 150.0°C)
When input range unit is Fahrenheit:
0 to 150 °F
(Range with a decimal point: 0.0 to 150.0°F)
When input is voltage or current:
0 to 1500

R/W

(19)

+95

Cooling Method

0: Air cooling
1: Oil cooling
2: Water cooling

R/W

(20)

+48

Cooling Proportional
Band

0.0 to 10.0 times
(Cooling proportional band is the product of this value
and the heating proportional band)

R/W

(21)

+98

Cooling Output ON/OFF
Hysteresis

When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current:
1 to 1000

R/W

(22)

+50

Overlap/Dead Band

When input range unit is Celsius:
-200.0 to 200.0°C
When input range unit is Fahrenheit:
-200.0 to 200.0°F
When input is voltage or current:
-2000 to 2000

R/W

(23)

+91

+168

Program Control Mode
Start Type

0: PV start
1: PVR start
2: SP start

R/W

(24)

+96

+173

Set Point (SP) when
Program Control Starts

When input is thermocouple/resistance thermometer:

Set point (SP) lower limit to set point (SP) upper limit

When input is voltage or current:

Linear conversion min. to linear conversion max.

R/W

(25)

+92

+169

Step Time Unit

0: Minute
1: Second

R/W

(26)

+93

+170

Program End Action

0: Terminate program control
1: Continue program control (Repeat)
2: Hold program control

R/W

(27)

+97

+174

Number of Repeats

0 to 10000 times

R/W