Appendix, Pid module function references, Ppendix – IDEC MicroSmart Pentra User Manual

Page 148: Pid module function references -1

Advertising
background image

A

PPENDIX

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

9-1

9: A

PPENDIX

This chapter describes the function references, output actions, and factory default settings of the PID module.

PID Module Function References

Control Action

PID control [with auto-tuning (AT)]
PI control
PD control (with auto-reset)
P control (with auto-reset)
ON/OFF control

Proportional term
(P)

Proportional band:

When input range unit is Celsius: 0 to 10000°C

(Range with a decimal point: 0.0 to 1000.0°C)
When input range unit is Fahrenheit: 0 to 10000°F

(Range with a decimal point: 0.0 to 1000.0°F)

When input is voltage/current: 0.0 to 1000.0%
Proportional gain: 0.00 to 100.00%
Note: The control action will be ON/OFF control when
proportional term is 0.

Integral time (I)

0 to 10000 seconds

Derivative time (D) 0 to 10000 seconds

Control period

1 to 120 seconds

ARW

0 to 100%

Reset

When input range unit is Celsius:
-100.0 to 100.0°C
When input range unit is Fahrenheit:
-100.0 to 100.0°F
When input is voltage/current:
-1000 to 1000

Output ON/OFF
hysteresis

When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage/current:
1 to 1000

Output
manipulated
variable (MV)
upper limit,
lower limit

When output type is relay or voltage:

Upper limit:
Output manipulated variable lower limit value to 100%

Lower limit:
0 to output manipulated variable upper limit value

When output type is current:

Upper limit:
Output manipulated variable lower limit value to 105%
Lower limit:
-5 to output manipulated variable upper limit value

Output
manipulated
variable
rate-of-change

0 to 100%/sec

Alarm

The alarm range can be configured with the alarm value. When the process
variable (PV) goes outside of the range, the alarm output turns on or off.
Alarm type can be selected from upper limit alarm, lower limit alarm, upper/lower
limits alarm, upper/lower limit range alarm, process low alarm, process high
alarm, upper limit alarm with standby, lower limit alarm with standby, upper/lower
limits alarm with standby, and no alarm action.
For details about the alarm, see pages 6-26 to 6-28.

Setting accuracy

Same with input error (See page 2-4)

Action

ON/OFF action

Hysteresis

When input is thermocouple or resistance thermometer:
0.1 to 100.0°C (°F)
When input is voltage/current:
1 to 1000

Output

Operating status (See page 5-9)

Alarm Delay time

0 to 10000 seconds