D

EVICE

A

LLOCATION OF

PID

M

ODULE

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

5-23

Program Parameters

Parameter

Description

R/W

Set Point (SP)

When input is thermocouple or resistance thermometer:

Set point (SP) lower limit to set point (SP) upper limit

When input is voltage or current input:

Linear conversion min. to linear conversion max.

R/W

Step Time

When step time unit is Minute:

0 to 6000 minutes

When step time unit is Second:

0 to 6000 seconds

R/W

Wait Value

When input range unit is Celsius:
0 to 100°C
(Range with a decimal point: 0.0 to 100.0°C)
When input range unit is Fahrenheit:

0 to 100°F

(Range with a decimal point: 0.0 to 100.0°F)
When input is voltage or current input:
0 to 1000

R/W

Proportional Term

Proportional band:
When input range unit is Celsius:
0 to 10000°C
(Range with a decimal point: 0.0 to 1000.0°C)
When input range unit is Fahrenheit:

0 to 10000°F

(Range with a decimal point: 0.0 to 1000.0°F)
When input is voltage or current input:
0.0 to 1000.0%
Proportional gain:
0.00 to 100.00%

R/W

Integral Time

0 to 10000 sec

R/W

Derivative Time

0 to 10000 sec

R/W

ARW (Anti-Reset Windup)

0 to 100%

R/W

Output Manipulated Variable
Rate-of-Change

0 to 100%/sec

R/W

Alarm 1 Value

See 5-18 for the valid range of alarm 1 to alarm 8 values.

R/W

Alarm 2 Value

R/W

Alarm 3 Value

R/W

Alarm 4 Value

R/W

Alarm 5 Value

R/W

Alarm 6 Value

R/W

Alarm 7 Value

R/W

Alarm 8 Value

R/W

Reserved

R/W

Output Manipulated Variable
Upper Limit

When output type is relay or voltage:
Output manipulated variable lower limit to 100%
When output type is current:
Output manipulated variable lower limit to 105%

R/W

Output Manipulated Variable
Lower Limit

When output type is relay or voltage:
0% to output manipulated variable upper limit
When output type is current:
-5% to output manipulated variable upper limit

R/W

Cooling Proportional Band
(CH0 only)

0.0 to 10.0 times
(Cooling proportional band is the multiplication of heating proportional band)

R/W

Overlap/Dead Band
(CH0 only)

When input range unit is Celsius:
-200.0 to 200.0°C
When input range unit is Fahrenheit:
-200.0 to 200.0°F
When input is voltage or current input:
-2000 to 2000

R/W