Pid m – IDEC MicroSmart Pentra User Manual

Page 76

Advertising
background image

C

ONFIGURING

PID M

ODULE USING

W

IND

LDR

F

C5A MicroSmart PID Module User’s Manual FC9Y-B1283

6-11

Input Parameters List when External SP Input is Selected

Control Registers

Offset from

the control

register

Parameter

Description

R/W

(1)

+55

Input Range
(External SP input)

0: Disabled (Note)
1: 4 to 20mA DC
2: 0 to 20mA DC
3: 1 to 5V DC
4: 0 to 1V DC
5: Cascade control (Note)
Note: Disabled and Cascade control cannot be selected
in the input range.

R/W

(2)

+139

PV Correction

-1000 to 1000

R/W

(3)

+140

PV Filter Time Constant

0.0 to 10.0 sec

R/W

(4)

+178

External SP Input Linear
Conversion Maximum
Value

External SP Input linear conversion min. to input range
upper limit of CH0

R/W

(5)

+179

External SP Input Linear
Conversion Minimum
Value

Input range lower limit of CH0 to external SP input linear
conversion max.

R/W

(6)

+177

External SP Input Bias

±20% of the external SP input linear conversion span

R/W

(7)

+142

Alarm 1 Type

0: No alarm action
1: No alarm action
2: No alarm action
3: No alarm action
4: No alarm action
5: Process high alarm
6: Process low alarm
7: No alarm action
8: No alarm action
9: No alarm action

R/W

+143

Alarm 2 Type

+144

Alarm 3 Type

+145

Alarm 4 Type

+146

Alarm 5 Type

+147

Alarm 6 Type

+148

Alarm 7 Type

+149

Alarm 8 Type

(8)

+114

Alarm 1 Value

See page 6-10 for the detail about alarm value range.

R/W

+115

Alarm 2 Value

+116

Alarm 3 Value

+117

Alarm 4 Value

+118

Alarm 5 Value

+119

Alarm 6 Value

+120

Alarm 7 Value

+121

Alarm 8 Value


(1)

(2)

(3)

(4)

(5)

(6)

(7)

(8)

(9)

(10)