2-2

FC5A MicroSmart PID Module User’s Manual FC9Y-B1283

(3) Control Output LED (OUT0, OUT1)

ON

: Control output is turned on.

OFF

: Control output is turned off.

Flashes : When current output is used, the LED flashes in a cycle of 125 ms

according to the duty ratio of the output manipulated variable (MV).

When output manipulated variable (MV) is 20%, the LED turns on for

25 ms and off for 100 ms continuously.

(4) Event Output LED (EVT0, EVT1)

ON

: Any alarm out of alarm 1 to alarm 8, loop break alarm is triggered.

OFF

: None of the alarms is triggered.

(5) Auto-tuning (AT)/Auto-reset LED (AT0, AT1)

Flashes : Auto-tuning (AT) or auto-reset is performing.

OFF

: Auto-tuning (AT) or auto-reset is stopped.

(6) Manual Mode LED (MT0, MT1)

ON

: Manual mode

OFF

: Auto mode

(7) Fixed Value Control Mode/Program Control Mode LED (F/P0, F/P1)

ON

: Program control mode

OFF

: Fixed value control mode

(8) Program Control RUN/HOLD LED (R/H0, R/H1)

ON

: Program control is performing, or while in fixed value control enabled.

Flashes : Program control is held, or power is restored.

OFF

: Program control is stopped, or while in fixed value control disabled.

(9) External SP Enable/Disable LED (R/L)

ON

: External SP input is enabled.

OFF

: External SP input is disabled.

(10) Terminal No.

Indicates terminal numbers.

(11) Cable Terminal

Spring clamp type terminal for connecting a cable.

(12) Expansion Connec

tor

Connects to the CPU module and other expansion modules.