App-2

IM MW100-17E

Appendix 2 Modbus Protocol

Modbus Protocol Specifications

The following are the Modbus specifications of the MW100.

Specifications

Description

Communication media

Ethernet, RS-232, or RS-422A/485

Control method

Ethernet

RS-232: None only

RS-422A/485: None only

Baud rate

Select 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200

bps

Start bit

1 bit, fixed

Data length

Select either 7 or 8 bits

Parity

Select Odd, Even, or None

Stop bit

Select either 1 or 2 bits

Data interval

24 bit time or less

Error detection

CRC-16

Transmission mode

RTU (remote terminal unit) mode only

Slave address

1~247