2-3

IM MW100-17E

Response

1

2

3

App

App

Index

2.1 Response Format

Data Sum

Sum value of binary data.

• Sum value is calculated only when “calculate sum” is set in the CS command. The value “0”

is stored in the sum value domain when “do not calculate sum” is set.

Flag

Flag value

Bits

Notation

0

1

Flag Meaning

7

BO

MSB

LSB

Byte order

6

CS

None

Y

Checksum

5

-

-

-

4

-

-

-

3

-

-

-

2

-

-

-

1

-

-

-

0

-

-

-

• The byte order is the data order of 2 or more bytes including the binary data portion. It

indicates that data is stored in the MSB (top byte) first or LSB (bottom byte) first.

• Checksum indicates whether a sum value is in the header sum and data sum domains, and

if the checksum value (CS) is 0, then 0 is stored in those domains.

• If a dash ( - ) is located in the notation or flag column, the bit is not used. The value is

indefinite.

Identifier

Identifier Binary Data Type

Format

0 Unspecified data

File

128 Unspecified data

Data

129 FIFO data

Data

130 The latest measured/computed data

Data

131 Latest output data

Data

132 FIFO read range

Data

Advertising