Ff output of measured/computed fifo data, Fl output of logs, alarm summaries, and status – Yokogawa Standalone MW100 User Manual
Page 49

1-42
IM MW100-17E
1.8 Output Commands
Example
Output the decimal place and units of the channels 1 to
5.
FE1,001,005
Explanation Set a first and last channel number so that the first is
less than or equal to the last.
FF
Output of Measured/Computed
FIFO Data
Setting
When p1=0
FFp1,p2,p3,p4,p5,p6,p7<terminator>
When p1=1
FFp1,p2<terminator>
p1 Output type
0
Outputs the FIFO data
1
Outputs the FIFO read range
p2 Measurement groups
1
Data from measurement groups 1
2
Data from measurement groups 2
3
Data from measurement groups 3
p3 First channel (001 to 060 and A001 to
A300)
p4 Last channel (001 to 060 and A001 to
A300)
p5 Read out start position
(-1, 1 to 99999999999)
-1
Latest read position
p6 Read out end position
(-1, 1 to 99999999999)
-1
Latest read position
p7 Max. number of read blocks (1 to
9999)
Example
Output the FIFO read range for measurement group 1.
FF1,1
Explanation • The oldest FIFO buffer data is overwritten with the
newest data in a cyclical manner.
• The output value of p1=1 (output FIFO read range)
is the allowable read range for p1=0 (FIFO data
output).
• Set a first and last channel number so that the first is
less than or equal to the last.
FL
Output of Logs, Alarm
Summaries, and Status
Setting
When p1=0
FLp1,p2,p3<terminator>
When p1=1
FLp1,p2,p3,p4<terminator>
When Outputting Logs
Setting
FLp1,p2,p3<terminator>
p1 Output type (0)
0
Log output
p2 Data type
ERROR
Operation error log
RECORD
Recording log
ALARM
Alarm summary
MESSAGE
Message summary
COM
General purpose
communication log
FTP_C
FTP client log
SMTP
Mail client log
DHCP
DHCP client log
SNTP
Time synchronization
client log
FTP_S
FTP server log
HTTP
HTTP server log
MODBUS_M
Modbus master log
MODBUS_C
Modbus client log
MODBUS_S
Modbus slave log
MODBUS_T
Modbus server log
CIP
CIP server log
PCCC
PCCC slave log
*
MATH
Computation status
*
CMD
Operation log
RECSTATUS Recording status
* Firmware version R3.02 or later
p3 Max. number of read blocks
ERROR
1 to 50
RECORD
1 to 250 (Or "1024" on
models with firmware version R3.02 or
earlier)
ALARM
1 to 256
MESSAGE
1 to 50
COM
1 to 200
FTP_C
1 to 50
SMTP
1 to 50
DHCP
1 to 50
SNTP
1 to 50
FTP_S
1 to 50
HTTP
1 to 50
MODBUS_M
1 to 50
MODBUS_C
1 to 50
MODBUS_S
1 to 50
MODBUS_T
1 to 50
CIP
1 to 50
*
PCCC
1 to 50
*
MATH
1
CMD
1 to 256
RECSTATUS 1
* Firmware version R3.02 or later
Example
Output 10 blocs of the operation error log.
FL0,ERROR,10
Explanation Outputs the log (records) saved to the instrument.
When Outputting Status
Setting
FLp1,p2,p3,p4<terminator>
p1 Output type (1)
1
Outputs status