1-22

IM MW100-17E

Query

AO[p1]?

Example

Set transmission output on channel 11 to 4-20 mA
relative to the measured values on channel 1.
AO011,AO,TRANS,20mA,4000,20000,0,001

Explanation • Specify output channels on p1.

• When entering the setting parameters of p5, p6, and

p7, exclude the decimal point.

• If the /M1 MATH function option is not included,

MATH channels (A001 to A300) cannot be set
(including queries) on p8. However, if the pulse input
module is installed, MATH channels (A001 to A060)
can be set (including queries).

When Setting PWM Channels

Setting

When using arbitrary output
AOp1,p2,p3,p4,p5,p6,p7,p8<terminator>
When using transmission output
AOp1,p2,p3,p4,p5,p6,p7,p8,p9<terminator>
p1 Channel range (001 to 060)
p2 Output type (PWM)
p3 Output method
TRANS

Transmission output

COM

arbitrary output

p4 Output range
1 mS

1 ms interval output

10 mS

10 ms interval output

p5 Lower limit of span (0.001% units,

0 to 100000)

p6 Upper limit of span (0.001% units,

0 to 100000)

p7 Pulse interval (specify as a

multiple)

1 to 30000 (both p4:1mS and 10mS same

range)

p8 Preset value (0.001% units,

0 to 100000)

p9 Reference channel
001 to 060 or A001 to A300

Query

AO[p1]?

Example

Set output on channel 12 to arbitrary output.
AO012,PWM,COM,1mS,0,100000,10,100000

Explanation • Specify output channels on p1.

• Channels set to SKIP are not output.
• If the /M1 MATH function option is not included,

MATH channels (A001 to A300) cannot be set
(including queries) on p9. However, if the pulse input
module is installed, MATH channels (A001 to A060)
can be set (including queries).

• When p4=10ms, p7=10, the pulse interval is 10 x 10

= 100 ms.

AP

Preset Operation Settings

Setting

APp1,p2,p3,p4<terminator>
p1 Channel range (001 to 060)
p2 Operation upon startup
LAST

Hold previous value

PRESET Output preset value
p3 Operation upon errors
LAST

Hold previous value

PRESET Output preset value
p4 Operation upon measurement stop,

computation stop, or transmission
stop (Firmware version R3.03 or
later)

LAST

Hold previous value

PRESET Output preset value

Query

AP[p1]?

Example

Set the operation upon startup for channel 1 to
PRESET, and operation upon errors to LAST.
AP001,PRESET,LAST

Explanation Specify output channels on p1.

SL

Event Action Settings

Setting

When p2=OFF
SLp1,p2<terminator>
When p2=DI
SLp1,p2,p3,p4,p5,p6<terminator>
When p2=ALARM
SLp1,p2,p3,p4,p5<terminator>
When p2=MEMORY
SLp1,p2,p3,p4,p5<terminator>
When p2=ALARM_CH
SLp1,p2,p3,p4,p5,p6,p7<terminator>
When p2=RELAY
SLp1,p2,p3,p4,p5,p6<terminator>
When p2=TIMER
SLp1,p2,p3,p4,p5,p6<terminator>
When p2=MATCH_TIME
SLp1,p2,p3,p4,p5,p6<terminator>
When p2=USER_KEY
SLp1,p2,p3,p4,p5,p6<terminator>

When Action Does Not Occur

Setting

SLp1,p2<terminator>
p1 Box number (01 to 30)
p2 Event type (OFF)

Query

SL[p1]?

Example

Set box number 01 to no action.
SL01,OFF