Output of modbus client logs (fl0, modbus_c) – Yokogawa Standalone MW100 User Manual

Page 80

Advertising
background image

2-30

IM MW100-17E

Output of Modbus Client Logs (FL0, MODBUS_C)

• Output using the FL command.
• Modbus client information logs are output.

Syntax

EACRLF
yy/mo/dd_hh:mm:ss_xxx_mmm...mCRLF
.........................................
ENCRLF

yy

Year (00 to 99)

mo

Month (01 to 12)

dd

Day (01 to 31)

hh

Hour (00 to 23)

mm

Minute (00 to 59)

ss

Seconds (00 to 59)

xxx

Command number (001 to 100, ---)

mmm...m Command status

(See “List of Character Codes Showing Modbus Master Command Statuses” on
page 2-25).

_

Blank

Example

EA
99/05/11 12:20:30 --- START
99/05/11 12:20:31 001 CONNECTING
99/05/11 12:20:32 001 VALID
EN

Output of Modbus Client Command Status (FL1, MODBUS_CC)

• Output using the FL command.
• Modbus client command status is output.

Syntax

EACRLF
SCAN = x, time = y msCRLF
xxx_mmm...mCRLF
.......................
ENCRLF

x

Number of successfully executed commands (0 to 100)

y

Time required to execute commands [ms] (0 to)

xxx

Command number (001 to 100)

mmm...m Command status

(See “List of Character Codes Showing Modbus Master Command Statuses” on
page 2-25).

_

Blank

2.2 ASCII Output