Yu mail contents settings, Yc e-mail alarm transmission settings, Yt time synchronization settings – Yokogawa Standalone MW100 User Manual

Page 41

Advertising
background image

1-34

IM MW100-17E

YU

Mail Contents Settings

Setting

When p1=TIME
YUp1,p2,p3,p4,p5<terminator>
When p1=ALARM
YUp1,p2,p3<terminator>
When p1 is neither TIME, ALARM, nor REPORT
YUp1,p2<terminator>

For other than report notification

Setting

YUp1,p2,p3,p4,p5<terminator>
p1 Send contents
ALARM Alarm notification
FILE

File creation notification

MEDIA

Media free space

notification

POWER

Startup notification

SYSTEM Setting error notification
TIME

Periodic report

p2 Recipient
OFF

Do not send

1

Send to recipient address 1

2

Send to recipient address 2

1_2

Send to recipient addresses

1 and 2

p3 Add instantaneous value data ON/OFF
p4 Send interval (1/2/3/4/6/8/12/24)[hours]
p5 Reference time (HH:MM)
HH

hours (00 to 23)

MM

Minute (00 to 59)

Query

YU?

Example

Set mail to recipients 1 and 2 daily at 18:00 with an
instantaneous value data attachment.
YUTIME,1_2,ON,24,18:00

For report notification

Setting

YUp1,p2,p3,p4,p5,p6,p7,p8,p9,p10,p11
<terminator>
p1 Sent contents
REPORT Notification of report

results

p2 Recipient
OFF

Do not send

1

Send to recipient address 1

2

Send to recipient address 2

1_2

Send to recipient addresses
1 and 2

p3 Send when creating hourly report

(OFF/ON)

p4 Send when creating daily report

(OFF/ON)

p5 Send when creating weekly report

(OFF/ON)

p6 Send when creating monthly report

(OFF/ON)

p7 Add maximum value data (OFF/ON)
p8 Add minimum value data (OFF/ON)
p9 Add average value data (OFF/ON)
p10 Add integral value data (OFF/ON)
p11 Add instantaneous value data (OFF/ON)

Query

YU?

Example

Add maximum and integral values when daily report is
created and send to recipient 1
YUREPORT,1,OFF,ON,OFF,OFF,ON,OFF,OFF,ON,
OFF

Explanation You cannot enter REPORT settings on products without

the /M3 report function option.

YC

E-Mail Alarm Transmission

Settings

Setting

YCp1<terminator>
p1 Channel structure (up to 100

characters)

Query

YC?

Example

Set the channels for mail alarm transmission judgement
to A001 to A005.
YCA001-A005

Explanation • See section 1.3 for the channel structure.

• You can specify measurement and MATH channels

(only with the /M1 MATH function option and when
the pulse input module is installed).

YT

Time Synchronization Settings

Setting

YTp1,p2,p3,p4<terminator>
p1 SNTP server name (up to 64

characters)

p2 Port number (1 to 65535)
p3 Reference time (HH:MM)
HH

hours (00 to 23)

MM

Minute (00 to 59)

p4 Query interval (3H/12H/24H) [hours]

Query

YT?

Example

Set time synchronization for once daily at 5:00.
YTsntp_server.abc.com,123,05:00,24H