App index, Ul validation of login function, Wc validation of client function – Yokogawa Standalone MW100 User Manual

Page 44: Ws validation of server function, Yq communication timeout settings

Advertising
background image

1-37

IM MW100-17E

Commands

1

2

3

App

App

Index

p6 Data Types
BIT

Bit Data (Firmware version

R3.04 or later)

INT16

Signed 16-bit integer

UINT16 Unsigned 16-bit integer
INT32_B Signed 32-bit integer (from

upper to lower)

INT32_L Signed 32-bit integer (from

lower to upper)

UINT32_B Unsigned 32-bit integer

(from upper to lower. )

UINT32_L Unsigned 32-bit integer

(from lower to upper)

FLOAT_B 32-bit floating decimal

(from upper to lower)

FLOAT_L 32-bit floating decimal

(from lower to upper)

p7 First channel (001 to 060, A001 to

A300, C001 to C300)

p8 Last channel (001 to 060, A001 to

A300, C001 to C300)

Query

WB[p1]?

Example

Set command number to 003, command to valid,

command type to READ, slave address to 1, register
address to 30001, data type to INT16, first channel to
C001, and last channel to C005.
WB003,ON,READ,1,30001,INT16,C001,C005

Explanation • You can set this command on products with the /M1

MATH function option.

• When p3 is READ, p7 and p8 can only be set to

C001 to C300.

• p7 and p8 can only be set to the same type of

channel.

• If the data type is INT16 or UNIT16, the maximum

number of channels that can be set from first to last
channel is 127. For other data types, the maximum
is 63.

UL

Validation of Login Function

Setting

ULp1<terminator>

p1 Login function ON/OFF

Query

UL[p1]?

Example

Enables the login function.

ULON

WC

Validation of Client Function

Setting

WCp1,p2<terminator>
p1 Client type
DHCP

DHCP client

FTP

FTP client

SMTP

SMTP client

SNTP

SNTP client

MODBUS_M

Modbus master

MODBUS_C

Modbus client

p2 Enable client function (ON/OFF)

Query

WC[p1]?

Example

Enable the FTP client.
WCFTP,ON

Explanation • The MODBUS_C of p1 can only be set with the /M1

MATH function option.

• The MODBUS_M of p1 can be set with the serial

interface option /C2 or /C3, or with the MATH
function option /M1.

WS

Validation of Server Function

Setting

WSp1,p2,p3<terminator>
p1 Server type
MODBUS

Modbus server

FTP

FTP server

HTTP

HTTP server

SNTP

SNTP server

GENE

MW100 dedicated protocol
server

DIAG

Maintenance/diagnostics
server

p2 Enable server function (ON/OFF)
p3 Port number (1 to 65535)

Query

WS[p1]?

Example

Enables FTP server on port number 21.
WSFTP,ON,21

YQ

Communication Timeout

Settings

Setting

YQp1,p2,p3<terminator>
p1 TCP keep alive (OFF/30 s)
p2 Timeout time (OFF, 1 to 120)[min]
p3 Modbus Delay Response (OFF, 10ms,

20ms, 50ms)(Firmware version R3.04 or
later)

OFF

No delay

0mS, 20mS, 50mS: Specify delay

Query

YQ?

Example

Set TCP keep alive to 30 seconds, communication
timeout time to 3 minutes, and Modbus Delay Response
to 10mS.
YQ30S,3,10mS

1.6 Setting Commands (Communication Related)

Advertising