Ml recording data length settings, Mr recording free space settings, Mx thinning recording operation settings – Yokogawa Standalone MW100 User Manual

Page 35: Mu setting save operation settings, Xk key lock settings

Advertising
background image

1-28

IM MW100-17E

Explanation • Set p5 (recording interval) to an integer multiple of the

measurement interval.

The recording interval can be set to 1, 2, 4, or 10 if

the measurement interval is 50 mS, 500 mS, or 5 S.

The recording interval can be set to 1, 5, or 10 if the

measurement interval is 200 mS.

The recording interval can be set to 1, 2, 5, or 10 for

all other measurement intervals.

ML

Recording Data Length Settings

Setting

MLp1<terminator>
p1 Data length when the recording

start timing is set to DIRECT under
recording operation

30 M (units of minutes)
1H/2H/3H/4H/6H/8H/12H (units of

hours)

1D/2D/3D/5D/7D/10D/14D/31D (units of

days)

Query

ML?

Example

Set the recording start time data length to 1 hour.
ML1H

MR

Recording Free Space Settings

Setting

MRp1<terminator>
p1 Recording time remaining on media set

for small media free space

1H/2H/3H/4H/5H (units of hours)

Query

MR?

Example

Set media free space to 2 hours.
MR2H

MX

Thinning Recording Operation

Settings

Setting

When p1=OFF
MXp1<terminator>
When p1 is not OFF
MXp1,p2,p3<terminator>
p1 Recording interval:
OFF (do not record)
4S/5S/10S/20S/30S (units of seconds)
1M/2M/3M/4M/5M/10M/20M/30M (units of

minutes)

1H (units of hours)
p2 Recording stop action
SINGLE Recording stops after

creating one file

FULLSTOP Recording stops when file is

full

ROTATE Continue recording by

deleting the old data

p3 Recording data length
30 M (units of minutes)
1H/2H/3H/4H/6H/8H/12H (units of

hours)

1D/2D/3D/5D/7D/10D/14D/31D (units of

days)

Query

MX?

Example

Set recording interval to 1H, recording operation to
FULLSTOP, and recording data length to 2D.
MX1H,FULLSTOP,2D

Explanation • p3 cannot be set to a time less than the p1 interval.

• The relationship between the measurement and

MATH intervals set on the input module and the
allowed thinning recording interval setting is shown
in the table below.

4S

5S

10S

20S

30S

1M

2M

3M

4M

5M

10M

20M

30M

1H

10ms, 50ms, 100ms

200ms, 500ms, 1s














2s












10s












Measurement Interval (Measurement Group/MATH Interval)

5s













20s









30s










60s









: Can be set, Blank: Cannot be set

Thinning

Recording

Interval

MU

Setting Save Operation Settings

Setting

MUp1,p2,p3,p4<terminator>
p1 Saving of channel related settings

OFF/ON

p2 Saving of recording related settings

OFF/ON

p3 Saving of communication related

settings OFF/ON

p4 Saving of other settings OFF/ON

Query

MU?

Example

Set so that all settings are saved.
MHON,ON,ON,ON

XK

Key Lock Settings

Setting

XKp1<terminator>
p1 Key lock OFF/ON

Query

XK?

Example

Key lock settings.
XKON

Explanation The setting is valid in Setting mode or Measurement

mode.