Special Data Values

During special statuses, measured and computed values are as shown in the table

below.

Special Data Value Type

Value

+OVER

0x7fff 0x7fff

–OVER

0x8001 0x8001

Measurement SKIP/computation OFF 0x8002 0x8002
Error

0x8004 0x8004

Uncertain

0x8005 0x8005

Note

• With output of the latest measured or computed data (FD1), a time stamp is added not

according to the time the data was created, but rather the time the command was issued.

• Measured/computed data values are stored as 32-bit integers.
• Alarm statuses are output without regard to the byte order specified in the BO command.

Output of the Latest Output Data

• Output using the FO1 command.

Format of Response to FO1 Command

'E'

'B'

CR

LF

Binary data

Data sum

Flag

Identifier

Header sum

Data length

4 bytes

Data block

Identifier=131

Latest outputted data

Data Block Structure

8 bytes

Year

Channel number
Channel number

Channel number

(Reserved)
(Reserved)

(Reserved)

Data value
Data value

Data value

Month

Day

Hours

Minute Second

(Reserved)

(Reserved)

Data Block Member Values

Member Name

Value

Year

00 to 99 (70 to 99: 1970 to 1999, 00 to 69: 2000 to 2069)

Month

1 to 12

Day

1 to 31

Hours

0 to 23

Minute

0 to 59

Second

0 to 59

Channel number

1 to 60: Output channel

Data value

–32767 to 100000

Unused

Undefined

2.3 Binary Output