2-14

IM MW100-17E

Output of Alarm Summaries (FL0, ALARM)

• Output using the FL command.
• Alarm summaries are output. Up to 256 past alarms are retained. If that number is

exceeded, old alarms are overwritten with new ones.

Syntax

EACRLF
yy/mo/dd_hh:mm:ss.ttt_cccc_ls_aaa..CRLF
...................................................
ENCRLF

yy

Yea

r (00 to

99)

mo

Month (01 to 12)

dd

Day (01 to 31)

hh

Hour (00 to 23)

mm

Minute (00 to 59)

ss

Seconds (00 to 59)

ttt

Miliseconds (000 to 999)

cccc

Channel numbers (001 to 060 or A001 to A300)

l

Alarm level (1 to 4)

s

Alarm type (

H

,

h

,

L

,

l

,

R

,

r

,

T

,

t

)

H

:

Upper limit alarm

h

:

Differential upper limit alarm

L

:

Lower limit alarm

l

:

Differential lower limit alarm

R

:

Upper limit on rate-of-change alarm

r

:

Lower limit on rate-of-change alarm

T

:

Delay upper limit alarm

t

:

Delay lower limit alarm

aaa..

Alarm status (off,on)

off

:

Alarm clear

on

:

alarm occurs

_

Blank

(Note)

When acknowledging alarm, AlarmAck is output in a position on and after the
cccc channel number.

Example

EA
05/04/01 12:20:00.000 001 1L on
05/04/01 12:20:00.000 A001 3t off
05/04/01 13:00:00.000 AlarmAck
EN

2.2 ASCII Output