Output of the Latest Measured/Computed Data

• Output using the FD command.

Syntax

EACRLF
DATE_yy/mo/ddCRLF
TIME_hh:mm:ssCRLF
s_ccccaaaauuuuuufdddddEfppCRLF
.........................................
s_ccccaaaauuuuuufeeeeeeeeEfppCRLF
.........................................
ENCRLF

yy

Year (00 to 99)

mo

Month (01 to 12)

dd

Day (01 to 31)

hh

Hour (00 to 23)

mm

Minute (00 to 59)

ss

Seconds (00 to 59)

s

Data status (N, D, S, O, E)

N: Normal, D: Differential input, S:Skip, O: Over, E: Error

_

Blank

cccc

Channel number (001 to 060 or A001 to A300)

aaaa

Alarm status (H, L, h, l, R, r, T, t, blank x 4 characters)

H (upper limit alarm), L (lower limit alarm), h (differential upper limit
alarm), l (differential lower limit alarm), R (upper limit on rate-of-change
alarm), r (lower limit on rate-of-change alarm), T (delay upper limit
alarm), t (delay lower limit alarm), blank character (no alarm)

uuuuuu

Unit information (output using 6 chars., left justified)

mV____: mV

V_____: V

^C____:°C

xxxxxx: (user specified char. string)

f

Data and exponent symbols (+, –)

ddddd

Data mantissa (measurement channel, 00000 to 99999)

-32767 to +65535: Normally allowed output range

+99999: +over, error (measurement error occurs), or indefinite

-99999: –OVER

eeeeeeee

Data mantissa (computation channel, 00000000 to 99999999)

-99999999 to +99999999

: Normally allowed output range

+99999999

: +OVER

-99999999

: –OVER

pp

Exponent (00 to 04)

2.2 ASCII Output