Martel Electronics BetaGauge 3II User Manual

Page 74

Advertising
background image

5-7

Advanced Display Modes

Defining Engineering Low/High Values

To define the engineering low and high values with
respect to the expected field instrument output signals,
do the following:

1.

After you define the field instrument type, the
following main linearization screen displays:

In the above example:
x = the channel number of the DC module,
yyyy = the current linearization mode of the DC
module channel.

2.

Press the function key corresponding to Eng and
the display screen prompts you for the field
instrument’s in/out low value. A sample screen is
shown below:

3.

Use the keypad numbers to enter a value equal to
the expected low electrical signal value of the field
instrument, then press the ENTER key.

4.

After you have specified an expected low electrical
signal value, the display screen individually
prompts you for the following field instrument
values:
 expected high electrical signal value
 engineering low value
 engineering high value

Repeat step 3 to enter values for each of the above
prompts.

CHx Mode: yyyy

Std

Eng

Sqrt

CHx Instr: Out Lo

Advertising