NORD Drivesystems BU0180 User Manual

Page 101

Advertising
background image

6 Parameterisation

BU 0180 GB-0914

Pre-series version

101

List of the possible functions of the digital inputs P420 [01]... [-04]

Value Function

Description

Signal

00

No function

Input switched off.

---

01

Enable right

The FI delivers an output signal with the rotation field right if a
positive setpoint is present: 0 → 1 Flank (P428 = 0)

High

02

Enable left

The FI delivers an output signal with the rotation field left if a
positive setpoint is present: 0 → 1 Flank (P428 = 0)

High

If the drive is to start up automatically when the mains is switched on (P428 = 1) a permanent High level for
enabling must be provided (supply terminal 21 with 24V).

If the functions "Enable right" and "Enable left" are actuated simultaneously, the FI is blocked.

If the frequency inverter is in fault status but the cause of the fault no longer exists, the error message is
acknowledged with a 1

→ 0 flank.

03

Change of rotation direction

Causes the rotation field to change direction in combination with
Enable right or left.

High

04

1

Fixed frequency 1

The frequency from P465 [01] is added to the actual setpoint
value.

High

05

1

Fixed frequency 2

The frequency from P465 [02] is added to the actual setpoint
value.

High

06

1

Fixed frequency 3

The frequency from P465 [03] is added to the actual setpoint value.

High

07

1

Fixed frequency 4

The frequency from P465 [04] is added to the actual setpoint value.

High

If several fixed frequencies are actuated at the same time, then they are added with the correct sign. In
addition, the analog setpoint (P400) and possibly the minimum frequency (P104) are added.

08

Param set switching

"Parameter set switchover 1"

Selection of the active parameter set 1…4 (P100)

High

09

Hold frequency

During the acceleration or deceleration phase, a Low level will
cause the actual output frequency to be "held". A High level
allows the ramp to proceed.

Low

10

2

Disable voltage

The FI output voltage is switched off; the motor runs down freely.

Low

11

2

Emergency stop

The FI reduces the frequency according to the programmed fast
stop time P426.

Low

12

2

Fault acknowledgement

Fault acknowledgement with an external signal. If this function is
not programmed, a fault can also be acknowledged by a low
enable setting (P506).

0

1

Flank

13

2

PTC resistor input

Only with the use of a temperature monitor (bimetal switching
contact). Switch-off delay = 2 sec, warning after 1 sec.

High

14

2, 3

Remote control

With bus system control, Low level switches the control unit to
control via the control terminals.

High

15

Jog frequency

1

The fixed frequency value can be adjusted using the
HIGHER/LOWER and OK keys (P113), if control is via the
SimpleBox or ParameterBox.

High

16

Motor potentiometer

As in setting 09, however, the frequency is not maintained below
the minimum frequency P104 and above the maximum frequency
P105.

Low

17

ParaSetSwitching

2

"Parameter set switchover 2"

Selec

tion of the active parameter set 1…4 (P100)

High

18

2

Watchdog

Input must see a High flank cyclically (P460), otherwise error
E012 will cause a shutdown. Function starts with the 1st high
flank.

0

1

Flank

19

Setpoint 1 on/off

Analog input switch-on and switch-off 1/2 (high = ON) of the first
I/O extension. The Low signal sets the analog input to 0% which
does not lead to shutdown when the minimum frequency (P104)
> than the absolute minimum frequency (P505).

High

20

Setpoint 2 on/off

High

21

... 28 reserved

29

Enable SetpointBox

-

Advertising