SK 180E Manual for frequency inverters

122

Pre-series version

BU 0180 GB-0914

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P541

Set relay

(set digital output)

S

000 ... FFF

(hex)

{ 000 }

This function provides the opportunity to control the relay and the digital outputs independently
of the frequency inverter status. To do this, the relevant output must be set to the function
"External control".

This function can either be used manually or in combination with a bus control.

Bit 0 = Digital output 1

Bit 1 = Digital output 2

Bit 2 = Bus/AS-i Out Bit 0

Bit 3 = Bus/AS-i Out Bit 1

Bit 4 = Bus/AS-i Out Bit 2

Bit 5 = Bus/AS-i Out Bit 3

Bit 6 = Bus Out Bit 4 / Out1 1. IOE

Bit 7 = Bus Out Bit 5 / Out2 1. IOE

Bit 8 = Bus Out Bit 6 / Out1 2. IOE

Bit 9 = Bus Out Bit 7 / Out2 2. IOE

Bit 10 = PZD - Bit 10

Bit 11 = PZD - Bit 13

Bits 8-11

Bits 7-4

Bits 3-0

Min. value

0000

0

0000

0

0000

0

Binary

hex

Max. value

1111

F

1111

F

1111

F

Binary

hex

Changes which are made to the settings are not saved in the EEPROM. After "Power ON" of
the frequency inverter, the parameter is therefore in the default setting.

Setting of the value via …

BUS:

The corresponding hex value is written into the parameter, thereby setting
the relay and the digital outputs.

SimpleBox:

The hexadecimal code is entered directly when the SimpleBox is used.

ParameterBox:

Each individual output can be separately called up in plain text and
activated.

P542

[-01]

[-02]

Set analog output

(Set analog output)

S

0.0 ... 10.0 V

{ all 0.0 }

[-01] =

First IOE, AOUT of the first I/O extension (SK xU4-IOE)

[-02] =

Second IOE, AOUT of the second I/O extension (SK xU4-IOE)

... only with
SK CU4-IOE or
SK TU4-IOE

The analog output of the FI can be set with this function, independently of the actual operating state.
To do this, the relevant analog output must be set to the function "External control" (P418 = 7).

This function can either be used manually or in combination with a bus control. The value set
here will, once confirmed, be produced at the analog output.

Changes which are made to the settings are not saved in the EEPROM. After "Power ON" of
the frequency inverter, the parameter is therefore in the default setting.