7.1 SimpleBox display

The SimpleBox displays an error with its number and the prefix "E". In addition, the current fault can be
displayed in array element [-01] of parameter (P700). The last error messages are stored in parameter
P701. Further information on inverter status at the time that the error occurs can be found in parameters
P702 to P706 / P799.

If the cause of the error is no longer present, the error display in the SimpleBox flashes and the error can be
acknowledged with the Enter key.

In contrast, warning messages are prefixed with "C" ("Cxxx") and cannot be acknowledged. They disappear
automatically when the reason for them is no longer present or the frequency inverter has switched to the
"Error" state. Display of the message is suppressed if the warning appears during parameterisation.

The current warning message can be displayed in detail at any time in array element [-02] of parameter (P700).

The reason for an existing disabled switch on cannot be displayed with the SimpleBox.

7.2 Table of possible error messages

7.2.1

Table of possible error messages in the frequency inverter

Display in the
SimpleBox

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details in
P700[-01] /
P701

E001

1.0

Overtemp. inverter
“Inverter overtemperature“
(inverter heat sink)

Error signal from output stage module (static)

Reduce ambient temperature <50°C or <40°C (see also
Section 8 Technical data)

Check control cabinet ventilation

Increase ambient temperature, > - 25°C

1.1

Overtemp. FI internal
“Internal overtemperature of FI“
(interior of inverter)

E002

2.0

Overtemp. Motor PTC
“Overtemperature of motor PTC“
(from thermistor)

Motor temperature sensor has triggered

Reduce motor load

Increase motor speed

Use external motor fan

2.1

Overtemperature motor I²t
”I²t motor overtemperature“

Only if I

2

t motor (P535) is

programmed.

I

2

t motor has triggered

Reduce motor load

Increase motor speed

2.2

Overtemp. Brake R.ext.
“Overtemperature of external
brake resistor“

Overtemperature via digital
input (

P420 […])={13}

Temperature monitor has triggered (only size 2)

Digital input is Low