6 Parameterisation

BU 0180 GB-0914

Pre-series version

105

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

18 = FI ready: The FI is ready for operation. After being enabled it delivers

an output signal.

High

19 = ... 29 reserved

30 = Digital-In 1 status*

High

Details for the

use of the

relevant bus

systems can be

found in the

applicable

supplementary

bus manual.

31 = Digital-In 2 status*

High

32 = Digital-In 3 status*

High

33 = Status Digital-In 4 / A-In1 *

High

34 = Status Digital-In 5 / A-In2 *

*) (P546[-

01]…[-03]) = 20

P435

[-01]

[-02]

Dig. out scaling

(Scaling of digital output)

-400 ... 400 %

{ 100 }

[-01] =

Digital output 1, Digital output 1 of the frequency inverter

[-02] =

Digital output 2, Digital output 2 of the frequency inverter

Adjustment of the limiting values of the output function. For a negative value, the output function
will be output negative.

Reference to the following values:

Current limit (3) = x [%]

P203 >Rated motor current<

Torque current limit (4) = x [%]

P203

P206 (calculated rated motor torque)

Frequency limit (5) = x [%]

P201 >Rated motor frequency<

P436

[-01]

[-02]

Dig. out. hysteresis

(Hysteresis of digital outputs)

S

1 ... 100 %

{ 10 }

[-01] =

Digital output 1, Digital output 1 of the frequency inverter

[-02] =

Digital output 2, Digital output 2 of the frequency inverter

Difference between switch-on and switch-off point to prevent oscillation of the output signal.

P460

Time watchdog

(Time watchdog)

S

0.0 / 0.1 ... 250.0 s
-0.1 ... -250.0 sec

{ 10.0 }

0.1 ... 250.0 = The time interval between the expected Watchdog signals (programmable

function of the digital inputs P420

– P425). If this time interval passes without a

pulse being registered, a switch off occurs with an E012 error message.

0.0 = Customer error: As soon as a high-low flank or a low signal is detected at a digital input

(function 18) the FI switches off with error message E012.

-0.1 ... -250.0 =

In this case the rotor rotation watchdog is active The time is defined by the
amount of the set value. There is no watchdog message when switched off.
After each enable, a puls must first come before the watchdog is activated.