NORD Drivesystems BU0180 User Manual

Page 108

Advertising
background image

SK 180E Manual for frequency inverters

108

Pre-series version

BU 0180 GB-0914

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P481

[-01]

...

[-10]

)

Funct.

BusIO Out Bits

(Function Bus I/O Out Bits

0 ... 39

{ [-01] = 18 }

{ [-02] = 08 }

{ [-03] = 30 }

{ [-04] = 31 }

{ [-05...-10] = 00 }

The bus I/O Out bits are perceived as multi-function relay outputs. They can be set to the same
functions (P434).

These I/O bits can also be used in combination with the AS interface (SK 190E) (Bit 0 … 3) or
the I/O extensions (SK xU4-

IOE) (Bit 4 … 5 and flags 1 … 2).

[-01] = Bus / AS-i Dig Out1

(Bus IO Out Bit 0 + AS-i 1)

[-02] = Bus / AS-i Dig Out2

(Bus IO Out Bit 1 + AS-i 2)

[-03] = Bus / AS-i Dig Out3

(Bus IO Out Bit 2 + AS-i 3)

[-04] = Bus / AS-i Dig Out4

(Bus IO Out Bit 3 + AS-i 4)

[-05] = Bus / IOE Dig Out1

(Bus IO Out Bit 4 + DO 1 of the first SK xU4-IOE (DigOut 02))

[-06] = Bus / IOE Dig Out2

(Bus IO Out Bit 5 + DO 2 of the first SK xU4-IOE (DigOut 03))

[-07] = Bus / 2nd IOE Dig Out1

(Flag1 + DO 1 of the second SK xU4-IOE (DigOut 04))

[-08] = Bus / 2nd IOE Dig Out2

(Flag2 + DO 2 of the second SK xU4-IOE (DigOut 05))

[-09] = Bit 10 BUS status word

[-10] = Bit 13 BUS status word

The possible functions for the Bus Out Bits can be found in the table of functions for the digital
outputs (P434).

P482

[-01]

...

[-10]

Stand. BusIO Out Bits

(Standardisation of Bus I/O Out Bits)

-

400 … 400 %

{ all 100 }

Adjustment of the limit values of the bus Out bits. For a negative value, the output function will
be output negative.

Once the limit value is reached and positive values are delivered, the output produces a High
signal, for negative setting values a Low signal.

[-01] = Bus / AS-i Dig Out1

(Bus IO Out Bit 0 + AS-i 1)

[-02] = Bus / AS-i Dig Out2

(Bus IO Out Bit 1 + AS-i 2)

[-03] = Bus / AS-i Dig Out3

(Bus IO Out Bit 2 + AS-i 3)

[-04] = Bus / AS-i Dig Out4

(Bus IO Out Bit 3 + AS-i 4)

[-05] = Bus / IOE Dig Out1

(Bus IO Out Bit 4 + DO 1 of the first SK xU4-IOE (DigOut 02))

[-06] = Bus / IOE Dig Out2

(Bus IO Out Bit 5 + DO 2 of the first SK xU4-IOE (DigOut 03))

[-07] = Bus / 2nd IOE Dig Out1

(Flag1 + DO 1 of the second SK xU4-IOE (DigOut 04))

[-08] = Bus / 2nd IOE Dig Out2

(Flag2 + DO 2 of the second SK xU4-IOE (DigOut 05))

[-09] = Bit 10 BUS status word

[-10] = Bit 13 BUS status word

Advertising