NORD Drivesystems BU0180 User Manual

Page 133

Advertising
background image

6 Parameterisation

BU 0180 GB-0914

Pre-series version

133

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter
set

P741

[-01]

...

[-10]

Process data Bus Out

(Process data Bus Out)

S

0000 ... FFFF

(hex)

This parameter provides information about the actual status word and the actual values that are
transferred via the bus systems.

For standardisation of actual values: See also (Section 9.9).

[-01] = Status word

Status word

[-02] = Actual value 1 (P543 [-01])

[-03] = Actual value 2 (P543 [-02])

[-04] = Actual value 3 (P543 [-03])

[-05] = res. stat. In Bit P481

"Resulting status of In Bit P481"

The displayed value depicts all bus Out
bit sources linked with OR.

[-06] = Parameter data 1

[-07] = Parameter data Out 2

[-08] = Parameter data Out 3

[-09] = Parameter data Out 4

[-10] = Parameter data Out 5

Data during parameter transfer.

P742

Database version

(Database version)

S

0 ... 9999

Displays the internal database version of the FI.

P743

Inverter type

(Inverter type)

0.25 ... 11.00kW

Displays the inverter power in kW, e.g. "1.50"

FI with 1.5 kW nominal power.

P744

Configuration level

(Configuration level)

0000 ... FFFF

(hex)

This parameter displays the special devices integrated in the FI. Display is in hexadecimal code
(SimpleBox, ControlBox, Bus System).

The display is in plain text when the ParameterBox is used.

High byte:

Low byte:

00

hex

01

hex

02

hex

03

hex

No extension

---

---

---

00

hex

01

hex

Standard I/O

(SK 180E)

ASI

(SK 190E)

P747

Inverter Volt. Range

(Inverter voltage range)

0 ... 2

Indicates the mains voltage range for which this device is specified.

0 = 100...120 V

1 = 200...240 V

2 = 380...480 V

Advertising